Skip to main content

§ 02.03Heating + heat pump — TX + OH

Furnace heat. Heat-pump heat. Sized for the day it gets cold.

A real heating-and-cooling load calc, not a square-footage rule of thumb. We pair a cold-climate heat pump with a gas furnace that takes the deep dips. The control hands the load back and forth automatically. We won't oversize because the catalog says to.

10 yrparts + labor warranty
§ 01Manual JReal load calc
§ 02Cold-climateHeat pump option
§ 0395–96%AFUE backup furnace
§ 04Auto cutoverBalance-point handoff
§ 05DFW + OhioBoth states
§ 06In-houseW-2 crew
The efficiency register

How much heat the gas actually delivers.

Each unit publishes an AFUE for furnaces or an HSPF2 for heat pumps. The number tells you how much of what you pay for ends up as heat in your house. Bigger is cheaper to run, each winter, for the life of the system.

80% AFUE gas furnacePre-1992 baseline
80%

For each $10 of gas, $2 goes up the flue. Common in older Texas homes. We replace these on the failure call.

95% AFUE gas furnaceCurrent condensing standard
95%RA spec

Sealed combustion, PVC vent, condensate drain. The right choice for an Ohio install where a heat pump alone will not reach the design day.

14 SEER2 heat pump (HSPF2 ~7.5)Entry-tier electric
~225%

Three units of heat for each unit of electricity at mild temps. Coefficient of performance drops as it gets colder — sizing matters.

Inverter heat pump (HSPF2 ~9.5)Texas standard install
~285%RA spec

A variable-speed compressor modulates load instead of slamming on and off. Pays back the upgrade on the cooling bill alone in DFW.

Cold-climate heat pump (HSPF2 10+)Northeast Ohio standard
~310%

Holds 70 percent of rated capacity at 5 degrees. Pair with a gas backup for the deep freezes and you carry most of the heating season on electricity.

Heat-pump percentages are coefficient-of-performance equivalents at mild outdoor temps. They drop as it gets colder — that is the reason we pair the heat pump with a gas backup, and the reason the balance-point math below matters.

The balance point

Where the heat pump hands off the load.

At each outdoor temperature, your heat pump puts out a certain amount of heat and your house loses a certain amount through the walls. Where those two curves cross is your balance point — the temperature where the heat pump stops carrying the load on its own and the gas furnace takes over. We calculate it for your house, not from a chart.

Local 99 percent design day
24°F
Heat-pump · gas handoff
32°F
Hours/yr below handoff
~80 hrs

Inverter heat pump runs 9 months a year. Gas furnace covers the deep freeze.

Heat-pump capacityHome heat lossBelow local design dayGas furnacecarries the loadHeat pumpcarries the loaddesign day 24°Fbalance point28°F10°F20°F30°F40°F50°F60°FOutdoor temperature25%50%75%100%
Five seconds at startup

What we measure each time your furnace fires.

On each install and each annual tune-up, we walk through the ignition sequence and put numbers on each step. A flame-rod current under spec is a single 40-dollar part and a 30-minute call. A cracked heat exchanger we miss is a 4,000-dollar callback in February.

  1. 01

    Pre-purge

    The inducer fan runs 30 seconds, clearing leftover gas before ignition. We measure the draft pressure switch closes within spec.

  2. 02

    Hot-surface ignite

    The igniter glows to 2400 degrees. The gas valve opens for 4 seconds. We verify the igniter resistance and the valve gas pressure on a manometer.

  3. 03

    Flame sense

    A flame rod confirms ignition with a microamp current. Below 1.5 microamps the board locks out for safety. We measure it, write it on the invoice.

  4. 04

    Heat exchanger check

    A rise reading across the supply and return. An out-of-spec rise points to airflow trouble or a cracked heat exchanger before it cracks worse.

  5. 05

    Blower handoff

    After the plenum reaches the high-limit setpoint, the blower starts. We time it. A late blower means a scorched heat exchanger in three winters.

Each reading goes on the invoice. If you sell the house, the next inspector reads it the same way we do.

Two markets · two playbooks

Same trade, different climate. Different spec.

We do not ship the same system to a Plano two-story and a Cleveland Cape. Sizing, equipment tier, and the handoff temp shift with the design day.

Mild winter · 24°F design day · cooling-dominant

The Texas play

Primary
Inverter heat pump · 18+ SEER2 · HSPF2 ≥ 9
Backup
80% AFUE gas furnace, single-stage
Handoff
Auto cutover at 32°F outdoor temp
Sizing rule
Sized to cooling load — backup carries the rare freeze
Why
You run heat about 10 weeks. The inverter pays itself back on the cooling bill.
Real winter · 4°F design day · heating-dominant

The Ohio play

Primary
Cold-climate inverter heat pump · HSPF2 ≥ 10
Backup
95–96% AFUE condensing gas furnace
Handoff
Auto cutover at 17°F outdoor temp
Sizing rule
Heat pump sized to about 75 percent of design-day load. Furnace covers the rest.
Why
Cold-climate units carry the season. Gas eats the deep dips. Strip heat stays out of the picture.

§ 12Continue the manual — related to this page

¶ In this trade

Five pages homeowners read next.

See all 4 in HVAC

This page is 02.03 in the manual · part of HVAC · 4 services

Open the HVAC hub →

§ 06Reach the dispatch desk

One system, sized for both seasons.

A free on-site measure, transparent itemized quote, and warranty terms in writing. No upsell, no high-pressure sales. We size by the math and register the warranty the same week.

(214) 578-9961